Prefabricated Metal Chimney - Quadra-Fire 41I-ACC Owner's Manual

Wood insert automatic combustion control
Hide thumbs Also See for 41I-ACC:
Table of Contents

Advertisement

41I ACC Wood Insert
E. Metal Heat Circulating Masonry
This insert conforms with the safety standard UL-1482 and
ULC S628 (Canada) in all respects and is approved to UL &
ULC safety standards for installation and use within a fire-
place with masonry chimney, in accordance with NFPA 211,
with a direct flue collar connection.
F. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
• M ust be minimum 6 inch (152mm) inside diameter of
high temperature chimney listed to UL 103 HT (2100
or ULC S628.
• M ust use components required by the manufacturer for
installation.
• M ust maintain clearances required by the manufacturer
for installation.
• R efer to manufacturers instructions for installation
•This insert is listed to UL 1482 Standard and is approved
for installation into listed factory-built zero clearance
fireplaces listed to UL 127 conforming to the following
specifications and instructions:
Flue Liner with Required Air Space
Stainless Steel Chimney Connector
Must Extend to Flue Liner
Minimum 8" (203mm) Masonry Thickness
in Front of Smoke Chamber
Minimum Clearance in Accordance with
Accordance with Insert
Combustible Floor
Figure 35.1
Page 36
Insert Listing
Floor Protection in
Listing
Generic Insert Model Shown in Illustration
•The original factory-built clearance fireplace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
•If the chimney is not listed as meeting HT requirements,
or if the factory built fireplace was tested prior to 1998, a
full height listed chimney liner must be installed from the
appliance flue collar to the chimney top.
•The liner must be securely attached to the insert flue collar
and the chimney top.
•The air flow of the factory-built zero-clearance fireplace
system must not be altered. The flue liner top support
attachment must not reduce the air flow for the existing
o
air-cooled chimney system.
F)
•No dilution air is allowed to enter the chimney.
1. Secure the fireplace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the fireplace.
3. Both methods must be removable and replaceable
for cleaning and re-installation.
7045-178
Airtight Insulated Clean-Out
Damper Plate Removed or
Fastened in Open Position
Seal with Non-
Combustible Material