Network/Access Control page in the UPS RMCARD201 web
If the community has write permission, the Client can complete some configuration tasks automatically. If the
Client cannot complete these tasks due to a permission limitation, the following settings must be configured
manually in the UPS RMCARD web or in the PDU web:
Outlet Off Delay Setting - Specify the necessary time for the Client to shut down the computer on the
Outlet/Outlet Configuration page in the PDU web.
Add the IP address of the Client computer to the Trap Receiver list of the UPS RMCARD/PDU on the
Network/Trap Notification page in the UPS RMCARD web or in the PDU web.
SNMP Trap Community
(This section is only applicable to Client with PDU or UPS RMCARD201)
The Client uses the community to authenticate the SNMP trap from a secure device. The community default
is public. The IP address of the Client computer must be added to the Trap Receiver list on the
Network/Trap
Notification page
matched.
of the UPS RMCARD201 and the PDU to ensure the community is
PowerPanel™ Business Edition