Connected Outlet: Indicates which power outlet of the UPS/PDU is supplying power to the Client
computer. Use the outlet preview to verify whether the Client computer is connected to the proper outlet.
The Identify button is only visible after the Client has established communication with the PDU, The
identification function helps to identify which outlet has the connected equipment. The PDU will blink the
outlet number on the LCD screen to verify the actual connection on the PDU matches when
the Identify button is pressed.
Identity function when connecting to PDU
Prevent Early Off: When the Client detects the PDU outlet, which is powering the Client computer, is
going to be shut off, the Client will prepare to shut down the hosted computer. If the necessary shutdown
time of the Client computer is more than the delay off time of the outlet, the Client will stop the computer
shutdown and signal the PDU to cancel to outlet turn off.
The following messages may be displayed:
Outlet should be assigned to the actual connection. Indicates the outlet assignment has not been
configured and the outlet assignment should be performed immediately. The outlet assignment must
precisely match the outlet being used by the Client on the UPS/PDU. If the wrong outlet is identified in
this section, a different device may lose power resulting an improper shutdown and loss of data. Because
the NCL (Non-Critical Load) outlets are only available on specific UPS models and can be configured to
power off early, the outlet being used by the Client must be configured correctly.
Network communication lost. Client can't monitor the assigned outlet. When the UPS/PDU is about
to turn off, the Client will be not aware of this condition from the UPS/PDU when the network
communication is lost. See Troubleshooting the Client's inability to communicate with the UPS
RMCARD/PDU/Agent section for more details to resolve this condition.
The assigned outlet is off. Please choose another outlet. The outlet assigned is not supplying power,
and the wrong outlet may have been identified. Verify the correct outlet is selected. .
The assigned outlet is has a turn off pending. The system will be shutdown soon. The outlet being
used by the Client computer will be switched off and stop supply power to the Client computer after the
delay is finished. Save all unsaved files and shut down the hosted computer as soon as possible.
System may not shutdown properly because the off-delay is too short. The Client detected the
connected outlet has insufficient time for the hosted computer to complete a shutdown. The off-delay
may be extended in the PDU web interface.