Energy Saving: When the utility power fails, the batteries will start discharging. If this option is enabled
and there is no output load, the UPS, will shut down to save battery power after discharging for 5 minutes.
The UPS will restart automatically and restore output after the utility power restores.
Low Battery Threshold: When the UPS supplies battery power and the remaining capacity is lower than
this threshold, the UPS will alarm.
Battery Test Period: The UPS will cyclically perform the battery test automatically to ensure the
batteries have full functional.
External Battery Pack: Sets the amount of external battery packs. This allows for an accurate runtime
estimate based upon the total number of batteries.
System
Cold Start: Sets the ability of the UPS can start in the absence of input power. When this option is
enabled the UPS can be turned on without having input power.
Short Circuit Recovery Detect: When the output of the UPS causes a short circuit, the output will turn
off immediately. If this option is enabled, the UPS will inspect the circumstance of short circuit for 3 times
in 30 seconds. If the short circuit is no longer present, the UPS will restore power. If the circumstance of
short circuit still remains, the UPS will not supply power.
Utility Power Failure Alarm: If this option is enabled, the UPS will issue an audible alarm when the
utility power fails.
Overload Alarm Threshold: When the output load exceeds this threshold, the UPS will issue an audible
alarm.
NCL Outlet
NCL stands for Non-Critical Load. Under the following conditions, the UPS will turn off the NCL outlet to
conserve battery power and maximize battery runtime for the remaining outlets:
Turn Off Threshold: When supplying battery power, the UPS will power off this NCL outlet if the
remaining battery capacity is lower than this threshold.
Turn Off Delay: When supplying battery power, the UPS will power off this NCL outlet after this delay
time is met.
Turn On Delay: When the utility power restores, the UPS will restore the output of this NCL outlet after
the delay time is met. This prevents excessive power consumption caused by all the connected
equipment starting at the same time.
Note: Not all models provide the same configurations. These configurations will vary by model.