Daikin DCS302C71 Operation Manual page 21

Central remote control
Hide thumbs Also See for DCS302C71:
Table of Contents

Advertisement

or
or
or
or
19
JH
Outdoor unit · Oil temperature sensor (Th5) system error
L0
Outdoor unit · Inverter system fault
L4
Outdoor unit · Inverter cooler fault
Outdoor unit · Ground circuit for compressor motor, short circuit,
L5
or power unit short circuit
L6
Outdoor unit · Ground circuit for compressor motor, short circuit
Outdoor unit · Compressor overload, compressor motor wire
L8
disconnection
L9
Outdoor unit · Compressor lock
LA
Outdoor unit · Power unit error
Outdoor unit · Transmission error between inverter and outdoor
LC
control unit
M1
Central controller: PC board fault
M8
Transmission error between central controllers
MA
Central controller: Incorrect combination
MC
Central controller: Address setting fault
P0
Insufficient gas (thermal storage)
P1
Outdoor unit · Power voltage imbalance, phase loss
P4
Outdoor unit · Power unit temperature sensor error
Pressure drop due to insufficient refrigerant, electric expansion
U0
valve fault, etc.
U1
Reversed or lost phase
U2
Power voltage error, momentary electrical stoppage
Transmission error between indoor unit/BEV unit and outdoor/BS
U4
unit, Transmission error between outdoor unit and BS unit
Transmission error between remote controller and indoor
U5
control unit
U5
Remote controller board fault or remote controller setting fault
U6
Transmission error between indoor units
Transmission error between outdoor units
U7
Transmission error between outdoor unit and ice thermal
storage unit
Transmission error between outdoor units
U7
(cooling/heating batch, low-noise operation)
Transmission error between master remote controller and slave
remote controller (slave remote controller error)
U8
Incorrect combination of indoor unit and remote controller within
a single system (model)
Transmission error between indoor unit/BEV unit and outdoor
unit within a single system
U9
Transmission error between BS unit and indoor unit/BEV unit and
outdoor unit within a single system
Incorrect combination of indoor, BS, and outdoor units within a
single system (model, number of units, etc.)
UA
Incorrect combination of indoor unit and remote controller
(remote controller in question) BS unit connection position fault
UC
Central control group numbers overlap
UE
Transmission error between indoor unit and central controller
Unset system, incorrect settings between BEV unit and
UF
indoor unit
English

Advertisement

Table of Contents
loading

Table of Contents