Chapter 11
Table 14. Electrical Input and Output
Nominal Input Voltage
Input Voltage Range
Nominal Output Voltage
Nominal Frequency
Regulation
Voltage Waveform
Overload Capability
DC Input Protection
Output Protection
Efficiency in Double-Conversion mode
Efficiency in Double-Conversion mode
(with Isolated Output)
Efficiency in Bypass mode (with Isolated
Output)
* 176–250 Vac for universal power modules producing 200 and 208 Vac nominal output voltage. 152–239 Vac for 120/208
and 127/220.
EATON Powerware
Specifications
This section provides the following specifications for the Powerware
+
9170
models:
S
Electrical input and output
S
Isolation
S
Model specifications
S
Environmental and safety
S
Battery
S
Weights and dimensions
200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac
176–276 Vac*
200–240 Vac or 100/200, 110/220, 120/208, 120/240, 127/220 Vac
Online: 50/60 Hz auto-sensing; output frequency tracks input frequency
to selectable limit (±0.1 to ±5.0 Hz; ±3.0 Hz default); switches to battery
operation outside this tolerance
On battery: 50 Hz or 60 Hz ±0.1 Hz
±3% load regulation (under any line, load, or battery condition)
Sine wave; <3% THD at rated linear loads, computer-grade power
150% for 10 seconds; 300% for 12 cycles
DC fuse and battery charger overvoltage limit network
Microprocessor-sensed overvoltage and overcurrent, with fuse backup
>88%
>84%
>96%
+
®
9170
UPS (3–18 kVA) User's Guide
S
164201393 Rev C www.powerware.com
99
Need help?
Do you have a question about the Powerware 9170+ and is the answer not in the manual?