Preparing For Installation - Cisco ME 3800X Installation Manual

Hide thumbs Also See for ME 3800X:
Table of Contents

Advertisement

Chapter 3
Installing and Removing AC and DC Input Power Supply and Fan Modules
Installing a DC Power Supply Module
This procedure is for installing an DC power supply module into the PSU 1 power supply module slot.
Repeat these steps to install a power supply module in the PSU 2 power supply slot.
To connect the switch to a DC input power source, follow these steps:
1.
2.
3.
4.
An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure
Warning
that no exposed portion of the DC-input power source wire extends from the terminal block plug.
Statement 122
Before connecting or disconnecting ground or power wires to the chassis, ensure that power is
Warning
removed from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the panel
board that services the DC circuit, switch the circuit breaker to the OFF position, and tape the switch
handle of the circuit breaker in the OFF position. Use a voltmeter to test for 0 (zero) voltage at the
power terminals on the chassis. Statement 196
Installation of the equipment must comply with local and national electrical codes.
Caution
We recommend that you use 14 or 16 AWG copper wiring for Network Equipment Building Systems
Note
(NEBS) installation, following the guidelines for DC power wiring in the central office.
You can use the grounding lug to attach a wrist strap for ESD protection during servicing.
Note

Preparing for Installation

You need these tools and equipment:
OL-22168-01
Preparing for Installation, page 3-7
Grounding the Switch, page 3-8
Installing the DC Power Supply Module in the Switch, page 3-10
Wiring the DC Input Power Source, page 3-10
Ratcheting torque Phillips-head screwdriver that exerts up to 36 inch-pounds (in-lb).
Crimping tool
Wire-stripping tools.
Copper ground wire (6 AWG, insulated or noninsulated) for the ground connection.
Two leads of 14 or 16 AWG copper wire.
Cisco ME 3800X and ME 3600X Switch Hardware Installation Guide