(5) Fixing the SSCNET ΙΙΙ cable with a cable tie
Fix the SSCNET ΙΙΙ cable to the installation surface of the
inverter using the accessory cable tie to prevent the
SSCNET ΙΙΙ cable from getting a damage caused by
vibration, etc. Gently slacken the cable with keeping a
larger radius than the minimum bend radius, and it should
not be twisted.
When performing wiring using the space between the inverter front cover and control circuit
terminal block, run the cable keeping the minimum bend radius or more so as not to subject the
cable to stress. In addition, take care that cables do not contact with the hot section. (Refer to page 24.)
After wiring, wire offcuts must not be left in the inverter. They may cause an error, failure or
malfunction.
Inverter installation
surface
Fix the SSCNET ΙΙΙ cable
using the accessory cable
clamp and cable tie.
CAUTION
WIRING
Inverter
Loose slack
3
31