C. DRYER ENCLOSURE REQUIREMENTS
Bulkheads and partitions should be made of noncombustible materials and must be located a minimum of
12-inches (18-inches or more is recommended for ease of installation, maintenance, and service) above the
dryer outer top, except along the front of the dryer which may be closed in if desired.
NOTE: Even though a minimum of 12-inches above the dryer outer top is acceptable, a clearance of
18-inches (or more) is suggested for ease of installation and service (electrical power
connections).
NOTE: When fire sprinkler systems are located above the dryers, a minimum of 12-inches above the
dryer outer top is required.
NOTE: Allowances must be made for opening the control door.
Dryers may be positioned sidewall to sidewall. However, allowances must be made for opening and closing of
the control door and the lint door. It is suggested that the dryer be positioned about 2 feet away from the nearest
obstruction for ease of installation, maintenance, and service (to be measured from the back guard.) Refer to
the illustration on the previous page for details.
NOTE: Air considerations are important for proper and efficient operation.
D. FRESH AIR SUPPLY REQUIREMENTS
Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An
unrestricted source of 840 cfm is necessary for each dryer. An unrestricted air entrance from the outdoors
(atmosphere) of a minimum of 1-1/2 square feet is required for each dryer. This area must be enlarged if
louvers or registers cover the opening. It is not necessary to have a separate make-up air opening for each
dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the
make-up air is distributed equally to the dryers. For example, for a bank of eight (8) dryers, a total make-up air
opening of 12 square feet is required. Two (2) openings measuring 2 feet by 3 feet (6 square feet) are acceptable.
(Refer to the illustration on the next page.)
Allowances must be made for remote or constricting passageways or where dryers are located at excessive
altitudes or predominantly low-pressure areas. The dryer must be installed with provisions for adequate
combustion and make-up air supply.
IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes.
Make-up air that is contaminated by dry cleaning solvent fumes will result in
irreparable damage to the motors and other dryer components.
10