Configuring the Redcare Secure unit

The unit is supplied pre-configured for pin only input mode and PSTN working. (Secure 2 /
Secure 3)
For most installations no further configuration will be required.
For alternative installation requirements the following configuration options are available.
There are two methods available to configure the unit. It can be configured with either a DTMF
phone or through a web console on a PC internet browser.
Configuration Method 1. Configuring with a DTMF Phone
1. Prepare wiring as described in Section 0.
2. For initial power-up and configuration, the following minimum connections are required:
a. DC Power
b. Antenna (for wireless operation)
3
Connect a DTMF phone to the units's alarm panel port J1000. An adapter is available from
Redcare. See fig 10
4
Short out the Config header J903 with a link.
5
Power up or power-cycle the unit.
6
Around 15 seconds after power on, the six rightmost LED's will flash providing a period of 20
seconds to lift the telephone receiver, receive dial tone and press the '#' key to enter
configuration Mode.
Note: Configuration Mode is terminated after five minutes, or when the installer hangs-up the
DTMF phone.
Note: If the Config header is left shorted once configuration mode is completed the unit will
not dialup or communicate at all.
Figure 10 – Adapter to connect a DTMF telephone to J1000 for configuration.
Installation, Maintenance and Operation Manual V24a (June 2012)
Page 14 of 40
 British Telecommunications plc 2012