General
Noise immunity to high
frequency emission
Climatic Conditions
Temperature
Operation
Storage/Transport
Relative humidity
Operation
Storage/Transport
Mechanical Environmental Conditions
Vibration
Operation
Transport (packaged)
Shock
Operation
Transport (packaged)
Special Features
Quality assurance
Servicing
Panel mounting
A.4

Certificates, Directives and Declarations for the TD Device

Certificates, Directives and Declarations for the TD Device
IEC 61131-2
The TD 100C and TD400C devices satisfy the requirements and criteria of the IEC directive
2004/108/EC standard (programmable controllers, part 2 on equipment requirements and
tests).
Notes on the CE Symbol
The following applies to the SIMATIC product described in this operating
instruction
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03
A.4 Certificates, Directives and Declarations for the TD Device
TD400C
6AV6640-0AA00-0AX1
10 V with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz
10 V/m with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz
3 V/m with 80% amplitude modulation at 1.4 GHz to 2 GHz
1 V/m with 80% amplitude modulation at 2.0 GHz to 2.7 GHz
0 to +50 °C
-20 to +60°C
85% (30℃), no condensation
95% (25℃ to 55℃), no condensation
Tested according to IEC 60068-2-6
5 Hz to 9 Hz, amplitude, 3,5 mm
9 Hz to 150 Hz, acceleration 9.8 m/s2
5 Hz to 9 Hz, amplitude 3.5 mm,
9 Hz to 500 Hz, acceleration 9.8 m/s2
Tested according to IEC 60068-2-27/29
Semisinusoidal: 150 m/s2 (15g), 11 ms
Semisinusoidal: 250 m/s2 (25g), 6 ms
In accordance with ISO 9001
Maintenance-free (no battery)
Accessories for panel mounting are enclosed