18. Observe the generator's ammeter (Figure 52) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.
0
Figure 52. Ammeter (Load)
19. The generator will run until manually stopped or an
abnormal condition occurs.
PAGE 46 — DCA-25SSIU — PARTS AND OPERATION MANUAL(STD) — REV. #7 (04/18//12)
DCA-25SSIU — GENERATOR SHUTDOWN PROCEDURE
40
20
60
75
A
ENGINE SHUTDOWN
To shutdown the generator, use the following procedure:
1. Switch both the MAIN, GFCI and LOAD circuit breakers
(Figure 53) to the "OFF" position.
Figure 53. Main, GFCI and Load
circuit breakers
2.
Set the engine throttle lever to (low) position.
3. Let the engine cool by running it for 3-5 minutes with no
load applied.
4. Turn the ignition key to 'STOP' (Figure 54).
Figure 54. Ignition Switch 'STOP'
5.
Remove the load from the UVW terminal strip.