Generator Shutdown Procedures - MULTIQUIP WHISPERWATT Series Operation Manual

60 hz generator isuzu bq-6wg1x diesel engine
Hide thumbs Also See for WHISPERWATT Series:
Table of Contents

Advertisement

WARNING
NEVER stop the engine suddenly except in an
emergency.
NORMAL SHUTDOWN PROCEDURE
1. Place the MAIN, GFCI and auxiliary circuit breakers
as shown in Figure 60 to the OFF position.
Figure 60. Main, Aux. and GFCI
Circuit Breakers (OFF)
2. Let the engine cool by running it at low speed for 3–5
minutes with no load applied.
3. Place the Auto Off/Reset Manual Switch (Figure 61)
in the OFF/RESET position.
AUTO
OFF/RESET
(CENTER)
Figure 61. Auto Off/Reset Manual Switch
(Off/Reset)
4. Verify that all status LEDs on the ECU control panel
are OFF (not lit).
5. Place the battery ON/OFF switch (Figure 62) in the
OFF position.
Figure 62. Battery Switch (OFF)
6. Remove all loads from the generator.
DCA400SSI4F/DCA400SSI4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (04/18/22) — PAGE 47

GENERATOR SHUTDOWN PROCEDURES

MANUAL
7. Inspect entire generator for any damage or loosening of
components that may have occurred during operation.
EMERGENCY SHUTDOWN PROCEDURE
NOTICE
The Emergency Stop Pushbutton Switch should only
be used to stop the engine in case of an emergency
or to lock out operation during service. The emergency
stop switch should NEVER be used for routine stopping
of the engine.
1. To stop the engine in the event of an emergency, push
the Emergency Stop Pushbutton Switch (Figure 63).
Figure 63. Emergency Stop Button
2. The emergency stop switch is a push-locked type
switch. The switch contact can only be released by
rotating the button in the clockwise direction. The
engine can not be restarted until the contact is released
(closed).
3. Place the MAIN, GFCI, and auxiliary circuit breakers
in the OFF position as shown in Figure 60.
AUTOMATIC SHUTDOWN SYSTEM
This unit is equipped with safety devices to automatically stop
the engine in the event of low oil pressure, approximately
14 psi (97 kPa), high water temperature, approximately
212°F (100°C), overspeed approximately +15%, or low
coolant level. The alarm message on the ECU displays to
signify the reason for the shutdown.
NOTICE
Before inspecting the generator, check that the
Auto/Manual switch is in the OFF/RESET position,
and place all circuit breakers in the OFF position. Allow
sufficient time for adequate cooling. When ready to
restart, complete all steps in the Generator Startup
Procedure section of this manual.