Generator Shut-Down Procedure - MULTIQUIP WHISPERWATT DCA-220SSVU Operation And Parts Manual

Whisperwatt series 50 hz generator
Table of Contents

Advertisement

DCA-220SSVU (50 HZ)— GENERATOR SHUT-DOWN PROCEDURES
WARNING - SHUTTING DOWN THE GENERATOR
NEVER stop the engine suddenly except in an emergency.
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
as shown in Figure 38 to the OFF position.
2. Place the engine speed switch (Figure 56) in the " LOW "
(down) position.
Figure 56. Engine Speed Switch (Low)
3. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
4. Place the MPEC Control Switch (Figure 57) to the
OFF/RESET position.
Figure 57. MPEC Control Switch (Off/Reset)
5. Verify that the all status LED on the MPEC display
are OFF (not lit).
6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening of
components that may have occured during operation.
DCA-220SSVU (50 Hz) — OPERATION AND PARTS MANUAL — REV. #0 (04/18/06) — PAGE 39
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
switch the MAIN , GFCI and LOAD (Figure 38) circuit
breakers to OFF position.
2. Place the MPEC Control Switch switch (Figure 57) to
the OFF/RESET position.