Table 3 Table 310-16 - Liebert 600T Series Installation Manual

Multi-module three phase 500 kva to 750 kva, 60 hz
Hide thumbs Also See for 600T Series:
Table of Contents

Advertisement

Table 3
Table 310-16
Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F)
Size
60°C
(140°F)
Types
TW*
UF*
AWG
kcmil
18
.......
16
.......
14
20†
12
25†
10
30
8
40
6
55
4
70
3
85
2
95
1
110
1/0
125
2/0
145
3/0
165
4/0
195
250
215
300
240
350
260
400
280
500
320
600
355
700
385
750
400
800
410
900
435
1000
455
1250
495
1500
520
1750
545
2000
560
Ambient
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown
Temp °C
21-25
1.08
26-30
1.00
31-35
.91
36-40
.82
41-45
.71
46-50
.58
51-55
.41
56-60
.......
61-70
.......
71-80
.......
* Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an
asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for
No.12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and
number of conductors have been applied.
1
Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code®, Copyright 1998, National Fire Protection
Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection
Association, on the referenced subject which is represented only by the standard in its entirety.
28
Wiring Inspection
Temperature Rating of Conductor. See Table 310-13.
75°C
90°C
(167°F)
(194°F)
Types
Types
FEPW*,
TBS, SA, SIS
RH, RHW*,
FEP*, FEPB*, MI,
THHW*,
RHH*, RHW-2,
THW*,
THHN*, THHW*,
THWN*,
THW-2, THWN-2,
XHHW*,
USE-2, XHH, XHHW*
USE*, ZW*
XHHW-2, ZW-2
Copper
.......
14
.......
18
20†
25†
25†
30†
35†
40†
50
55
65
75
85
95
100
110
115
130
130
150
150
170
175
195
200
225
230
260
255
290
285
320
310
350
335
380
380
430
420
475
460
520
475
535
490
555
520
585
545
615
590
665
625
705
650
735
665
750
Correction Factors
above by the appropriate factor shown below.
1.05
1.04
1.00
1.00
.94
.96
.88
.91
.82
.87
.75
.82
.67
.76
.58
.71
.33
.58
.......
.41
60°C
75°C
(140°F)
(167°F)
Types
Types
TW*
RH*, RHW*,
UF*
THHW*,
THHN*, THHW*,
THW*,
THW-2, THWN-2,
THWN*,
XHHW*,
USE*
Aluminum or Copper-Clad Aluminum
.......
.......
.......
.......
.......
.......
20†
20†
25
30†
30
40
40
50
55
65
65
75
75
90
85
100
100
120
115
135
130
155
150
180
170
205
190
230
210
250
225
270
260
310
285
340
310
375
320
385
330
395
355
425
375
445
405
485
435
520
455
545
470
560
1.08
1.05
1.00
1.00
.91
.94
.82
.88
.71
.82
.58
.75
.41
.67
.......
.58
.......
.33
.......
.......
1
Size
90°C
(194°F)
Types
TBS, SA, SIS,
AWG
kcmil
RHH*, RHW-2,
USE-2,
XHH, XHHW*,
XHHW-2, ZW-2
.......
.......
.......
.......
.......
.......
25†
12
35†
10
45
8
60
6
75
4
85
3
100
2
115
1
135
1/0
150
2/0
175
3/0
205
4/0
230
250
255
300
280
350
305
400
350
500
385
600
420
700
435
750
450
800
480
900
500
1000
545
1250
585
1500
615
1750
630
2000
Ambient
Temp °F
1.04
70-77
1.00
78-86
.96
87-95
.91
96-104
.87
105-113
.82
114-122
.76
123-131
.71
132-140
.58
141-158
.41
159-176