Table 7 - Liebert NXL Installation Manual

250-400kva, 60hz, three-phase, single-module
Hide thumbs Also See for NXL:
Table of Contents

Advertisement

Table 7

Liebert NXL UPS specifications (continued)
Physical Parameters and Standards, in (mm)
Environmental Parameters
*
Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
** Depth dimensions include the front door and rear panel.
Width, With Side Panels *
SMS
Weight, Unpacked, lb. (kg) approx.
1+N
Weight, Unpacked, lb. (kg) approx.
Max heat Dissipation, Full Load, BTU/hr
Cooling Air CFM
Front Door Opening (for serviceability)
Degree of Protection for UPS Enclosure
Minimum Clearance, Top, in (mm)
Minimum Clearance, Back, in (mm)
Minimum Clearance, Sides, in (mm)
Location of Cable Entrance
Standards and Conformities
Storage Temperature Range, °F (°C)
Operating Temperature Range, °F (°C)
Acoustical Noise, dBA
Relative Humidity
Maximum Altitude Above MSL, ft (m)
250
71.8 (1823)
Depth **
33.5 (850)
Height
3965 (1798)
4040 (1833)
53,592
5894
Color
IP 20 (with and without front door open)
UL 1778, 4th Ed
CSA 22.2 107.3
FCC Part 15, Class A
FCC, Class A—Standard
IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3
ISTA Procedure 1H
WEEE
32 to 104 (0 to 40) (UPS)
Non-Condensing (Operating and Non-Operating)
4920 (1500) (as per IEC 62040/3) - 1% Max kW
derate / 328 rise between 4921-9842
(100m rise between 1500-3000m)
32
Specifications
300
78.5 (1993)
78.5 (1993)
33.5 (850)
39.4 (1000)
76.8 (1950)
4840 (2195)
6280 (2849)
4915 (2229)
6380 (2894)
63,036
77,638
5894
7092
Black (ZP-7021)
More than 180°
24 (610)
0
0
Top or Bottom
-13 to 158 (-25 to 70)
68
95% or less
400

Advertisement

Table of Contents
loading