Hearth Extensions/Wall Shields - Lennox EST-36 Installation Instructions Manual

Estate series 36"/42"/50" wood-burning fireplaces
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • ESTATE™ SERIES WOOD-BURNING FIREPLACES • MODELS EST-36, EST-42, EST-50 • INSTALLATION INSTRUCTIONS
models
a
20"
Est-36
(508mm)
20"
Est-42
(508mm)
20"
Est-50
(508mm)
Figure 47
hearth Extensions and Wall shields
A hearth extension must be installed with all
fireplaces. Its purpose is twofold: 1) to protect
a combustible floor in front of the fireplace
from both radiant heat and sparks; and 2) to
distinguish the prescribed hearth extension area
from other unprotected surfaces.
The hearth extension must extend beyond the
front at least 20" (508 mm) and both sides at
least 12" (305 mm) (Figure 47 ). Use a hearth
extension constructed of a durable noncombus-
tible material having an equal or better (lower k
value) insulating value of k = .84 BTU IN/FT
°F or a thermal resistance that equals or exceeds
r = 1.19 HR °F FT
/BTU IN. With these values,
2
determine the minimum thickness/material
required using the formulas shown at right.
When using multiple materials, see the next
page.
note: Any noncombustible material whose k
value is less than .84 or whose r value is more
than 1.19 is acceptable.
If the fireplace is installed on a combustible
floor, use the metal safety strips (provided) on
the floor extending half under the fireplace and
half under the hearth extension.
A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening (Figure 48). Use a 36" W
x 36" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than
k = .54 BTU IN/FT
HR °F. At no time may a
2
perpendicular side wall be located closer than
9" from the fireplace opening.
If fireplace is installed diagonally across a 90°
corner; no wall shields are required.
b
c
d
36"
12"
60"
(914mm)
(305mm)
(1524mm)
42"
12"
60"
(1066mm)
(305mm)
(1524mm)
50"
12"
74"
(1880mm)
(1270mm)
(305mm)
methods of determining hearth Extension and Wall shield Equivalents
To determine the thickness required for the alternate material, use the "k formula"
when the "k" value is known, and use the "r formula" when the "r" value is known.
k
r
t
t
k
r
t
ExamplE: What is the minimum required thickness when using Micore 160 for the
HR
2
fireplace hearth extension?
NOTE: An asterisk (*) indicates a value taken from Table 1 (next page).
using the "k formula" (when the "k" value is known):
minimum
thickness of
alternate
material (t
t
(inches)
m
t
(inches)
m
.416 (inches) =
ansWEr: The minimum required thickness of the Micore 160 is .417";
therefore, round up to nearest standard thickness available, which is 1/2".
using the "r formula" (when the "r" value is known):
minimum
thickness of
alternate
material
t
(inches)
m
t
(inches)
m
.416 (inches) =
ansWEr: The minimum required thickness of the Micore 160 is .417";
therefore, round up to nearest standard thickness available, which is 1/2".
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
C
= k value per inch of alternate material
m
= r value per inch of alternate material
m
= minimum thickness required for alternate material
m
= standard thickness of the alternate material
s
= k value per inch of listed material
l
= r value per inch of listed material
l
= minimum thickness of listed material
l
k-value (per Inch) of
alternate material (k
=
k-value (per inch)
)
of listed material (k
m
k
=
m
*.84
*.35
=
*.84
.416
r-value (per inch)
=
of listed material
r-value (per inch)
of alternate material
r
=
l
r
m
=
*1.19
*2.86
.416
C
B
D
specified min.
)
x
thickness
m
of listed
material (t
)
)
l
m
x
t
l
x
1"
x
1"
specified min.
x
thickness
of listed
material
x
t
l
x
1"
x
1"
A
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Estate st-36Estate est-42Estate est-50

Table of Contents