DISPLAY DURATION SET
<3 MIN>
>∆/∇: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the 'up' or 'down' arrow key to move the marker between the two available idle
mode times. Press the ENTER key to save the change or press the MENU key to exit
to the main menu and discard the change.
Note: If any of the following conditions occur, the LCD-Idle Mode will be inhibited
and the LCD will remain on continuously:
1) The UPS has received an emergency-off command.
2) The UPS is in battery discharge mode.
3) A fault has been detected in the main unit.
4) The UPS is in an overload condition.

6.15.4 Run Switch Select

Press the MENU key to access the menu data screens and press the 'down' arrow
key to scroll to the run switch select setting screen display:
RUN SWITCH SELECT
>*F1: DATA SET MODE
>∆/∇: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
>∆/∇: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the 'up' or 'down' arrow key to move the marker between the two "RUN
SWITCH" selections Press the ENTER key to save the change or press the MENU
key to exit to the main menu and discard the change. (Must have Remote S/U
option.)

6.15.5 Serial Com Station Address

Press the MENU key to access the menu data screens and press the 'down' arrow
key to scroll to the run switch select setting screen display:
SER COM STATION ADDR
STATION ADDRESS:
>*F1: DATA SET MODE
> ∆/∇: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
SER COM STATION ADDR
STATION ADDRESS:
>∆/∇: CHANGE DATA
>ENTER: ACCEPT CHANGE
TOSHIBA
30 MIN
<LOCAL>
REMOTE
RUN SWITCH SELECT
<LOCAL>
REMOTE
31H
31H
36