Installation Instructions
Temperature Limiting
1 2 3 4 5 6
ON
ON
OFF
OFF
Auxiliary Controls
Diagnosis Switch
ON
ON
OFF
OFF
Auxiliary Controls
18
Temperature limiting can reduce
energy costs by limiting the lowest
temperature that can be set on
cooling and the highest tempera-
ture that can be set on heating.
Temperature limiting is controlled
by setting the first six auxiliary
switches.
The first three are used to select
cooling range limits and the next
three are used to select heating
range limits.
The Zoneline has a diagnosis
feature. When switch 13 is moved
to the ON (up) position, the unit
will go through an operations
check of all components which
13
takes about two minutes. This diag-
nostic tool is intended for use by a
qualified technician.
COOLING LIMITS
Limit Switch
Temp Range
Up/On
NONE
1
1 & 2
2
2 & 3
1 & 2 & 3
1 & 3
3
HEATING LIMITS
Limit Switch
Temp Range
Up/On
NONE
4
4 & 5
5
5 & 6
4 & 5 & 6
4 & 6
6
F.
62 to 85
64 to 85
67 to 85
69 to 85
71 to 85
73 to 85
75 to 85
77 to 85
F.
60 to 85
60 to 80
60 to 76
60 to 74
60 to 73
60 to 71
60 to 69
60 to 67