1507/1503
Users Manual

Specifications

Need intro paragraph here

General Specifications

Maximum Voltage Applied to any Terminal ........600 V ac rms or dc
Storage Temperature ..........................................-40 °C to 60 °C (-40 °F to 140 °F)
Operating Temperature.......................................-20 °C to 55 °C (-4 °F to 131 °F)
Temperature Coefficient......................................0.05 x (specified accuracy) per °C for temperatures < 18 °C or > 28 °C
Relative Humidity ................................................Noncondensing
Vibration ..............................................................Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Shock ..................................................................1 meter drop per IEC 61010-1 2
Electromagnetic Compatibility.............................In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997).
Safety ..................................................................Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and
Certifications .......................................................CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1
Batteries ..............................................................Four AA batteries (NEDA 15A or IEC LR6)
Battery Life ..........................................................Insulation test use: Tester can perform at least 1000 insulation tests with fresh alkaline
Size .....................................................................5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L)
Weight .................................................................550 g (1.2 lb.)
20
(< 64 °F or > 82 °F)
0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F)
0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F)
0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F)
nd
IEC/EN 61010-1 2
Edition for measurement category IV 600 V (CAT IV)
nd
2
Edition
batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty
cycle of 5 seconds on and 25 seconds off. Resistance Measurements: Tester can perform
at least 2500 earth-bond resistance measurements with fresh alkaline batteries at room
temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25
seconds off.
nd
Edition (1 meter drop test, six sides, oak floor)