APPLYING POWER (Top View)

Notes:
Only 1 power supply must be connected to power for minimal operation. For redundant power
operation, V
1
draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.
The Fault pins on the power connector can be used for an alarm contact. The current carrying
capacity is 1A at 24VDC. It is normally open and the relay closes when a fault condition occurs.
These pins can be used to connect an external warning device such as a light in order to provide an
external alarm. The conditions for generating a fault condition (closing the relay) can be configured
through software.
Recommended 24V DC Power Supplies, similar to: N-Tron's P/N NTPS-24-1.3 (NOTE: Not appropriate
for use with M12, POE, and HV models.):
Input AC 115/230V
Output DC 24-28V
Output Current 1.3A @ 24V
(Revised 2012-05-01)
and V
inputs must be connected to separate DC Voltage sources. This device will
2
1.0A @ 28V
Unscrew & Remove the DC Voltage Input
Plug from the Power Input Header
Install the DC Power Cables into the Plug
(observing polarity).
Plug the Voltage Input Plug back into the
Power Input Header.
Tightening torque for the terminal block
power plug is 0.5 Nm/0.368 Pound Foot.
Verify the Power LED stays ON (GREEN).
Power 30W
35 mm DIN-Rail Mountable
Dimensions: 45X75X91 mm