Environmental specifications

Feature
Operating temperature
Nonoperating
temperature
Relative humidity
Operating altitude
Nonoperating altitude
Audible noise

REPO port specifications

The REPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.
Specification
10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
-25°C to 55°C (-13°F to 131°F)
20% to 80%; noncondensing
Up to 2,000 m (6,600 ft) above sea level
15,000 m (49,212 ft) above sea level
Less than 50 dBA, normal operation
Less than 55 dBA, on battery power
Specifications 53