Alarm number Alarm name
Utility Not Present
59
Battery DC Over Voltage
68
To Bypass Command
94
From Bypass Command
95
On Manual Bypass
143
Service Battery
149
Output Overload Level 2
159
Output Overload Level 3
162
UPS On Battery
168
UPS On Bypass
169
UPS Off
170
UPS On Command
172
UPS Off Command
173
Battery Shutdown
174
UPS Control Power ON
181
Battery Test Failed
191
Site Wiring Problem
194
Battery Disconnected
199
UPS System Normal
237
ABM State Charging
1600
ABM State Floating
1601
ABM State Resting
1602
ABM State OFF
1603
Clock set done
1999
Alarm description
The utility level has fallen below the Utility Not Present
threshold.
Battery voltage levels have exceeded the maximum
allowable limits.
A request to transfer to Manual Bypass Mode
received from software.
A request to transfer to Operate Mode is received
from software.
The UPS is manually commanded to switch to bypass
and will remain in bypass until commanded out of
bypass.
A faulted battery string is detected, and the battery
charger has been disabled until it is replaced.
Load levels are greater than a level 2 Overload
condition and less than a level 3 Overload condition.
Load levels are greater than a level 3 threshold.
The UPS is operating from batteries.
The UPS is operating from bypass.
The UPS is in Standby mode or Fault mode.
Indicates a manually requested transition from
Standby to Operate. This event is not triggered for
auto restarts.
A UPS OFF command was received from remote S/W
and causes the UPS to open up all output relays and
shed the load.
The UPS has shut down due to running on battery for
a long enough time to exhaust the battery capacity.
The UPS is powered up.
A weak battery string is detected during the battery
test.
The difference between ground and neutral voltage is
less than 30 V.
Battery voltage is lower than the batteries
disconnected level defined for this UPS. If ERMs are
attached, this alarm does not trigger unless the ERMs
are also disconnected, since they are paralleled with
the battery bus.
The UPS has started or returned to its normal
operating mode of operation and no alarms are
active.
The status of ABM charge mode is constant current
charging.
The status of ABM charge mode is floating.
The status of ABM charge mode is resting.
The status of ABM charge mode is OFF or disabled. Event
The UPS real time clock setting has been adjusted.
Alarm type
Notice
Alarm
Event
Event
Notice
Alarm
Alarm
Alarm
Notice
Notice
Event
Event
Event
Alarm
Event
Notice
Alarm
Alarm
Event
Event
Event
Event
Event
Troubleshooting 45