11. Field Setting; Test Operation - Daikin FXMQ07PVJU Installation Manual

Vrv system inverter air conditioners
Hide thumbs Also See for FXMQ07PVJU:
Table of Contents

Advertisement

No. 3 system: When including BS unit
Power supply
single phase
Outdoor unit
60Hz 208/230V
L
L
1
2
IN/D
F
F
1
2
L
L
P
P
1
2
1
2
Indoor unit A
Remote controller
[ PRECAUTIONS ]
1. Make sure that the ground fault circuit interrupter is
designed to protect the air conditioner from ground faults,
overloads, and short-circuiting.
2. The remote controller wiring (P1 and P2) and transmission
wiring (F1 and F2) have no polarity.
10-3 CONTROL BY 2 REMOTE CONTROLLERS (Con-
trolling 1 indoor unit by 2 remote controllers)
• Set one of the remote controllers to main and the other to sub
in the case of remote control with two remote controllers.
Switching Main/Sub
(1) Insert a
screwdriver into the clearance between the
grooves of the lower casing and the upper casing to remove
the upper casing. (2 grooves) (The remote controller PCB is
attached to the upper casing.)
Insert the screwdriver here and gently work
off the upper part of remote controller.
14
BS unit
OUT/D
OUT/D
IN/D
F
F
F
F
F
F
1
2
1
2
1
2
F
F
T T
1
2
1
2
P
P
1
2
(option)
Upper part of
remote controller
Lower part of
remote controller
(2) Set the main/sub switch on one of the remote controller
PCBs to sub. (Keep the switch of the other remote controller
PCB set to main.)
(Factory setting)
Only one remote
controller needs to be
changed if factory
settings have
remained untouched.
10-4 COMPUTERISED CONTROL (FORCED OFF
AND ON/OFF OPERATION)
(1) Wire specifications and how to perform wiring
• Connect the input from outside to terminals T1 and T2 of
the terminal block for remote controller.
F2
T1
FORCED
OFF
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
AWG18-16
Length
Max. 328 ft
Contact that can ensure the minimum appli-
External terminal
cable load of 15 V DC, 1 mA.
(2) Actuation
• The following table explains FORCED OFF and ON/OFF
OPERATIONS in response to Input A.
FORCED OFF
Input "ON" stops operation (impossible by
remote controllers.)
Input OFF enables control by remote con-
troller.
(3) How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to
select operation.
10-5 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional control-
lers for centralized control.

11. FIELD SETTING

NOTE
• Before the test operation of the outdoor unit as explained in
12. TEST OPERATION, be sure to make the following field
settings as explained in 11. FIELD SETTING.
S
S
M
Remote controller
PC board
S
M
T2
Input A
ON/OFF OPERATION
Input OFF → ON turns
ON unit.
Input ON → OFF turns
OFF unit.