Indoor Unit Installation - Daikin FXMQ07PVJU Installation Manual

Vrv system inverter air conditioners
Hide thumbs Also See for FXMQ07PVJU:
Table of Contents

Advertisement

(2) Mount the canvas ducts to the air outlet and inlet so that the
vibration of the air conditioner will not be transmitted to the
duct or ceiling. Apply a sound-absorbing material (insula-
tion material) to the inner wall of the duct and vibration insu-
lation rubber to the hanging bolts (refer to 8. DUCT WORK).
(3) Open installation holes (if the ceiling already exists).
• Open the installation holes on the ceiling. Lay the refrig-
erant piping, drain piping, power line, transmission wir-
ing, and remote controller wiring for the piping and wiring
connection port of the unit.
In the case of the installation of a wireless remote con-
troller, refer to the installation manual provided with the
wireless remote controller.
Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN
PIPING WORK, and 10. WIRING EXAMPLE AND HOW
TO SET THE REMOTE CONTROLLER.
• The ceiling framework may need reinforcement in order
to keep the ceiling horizontal and prevent the vibration of
the ceiling after the installation holes are opened. For
details, consult your construction or interior contractor.
(4) Install the hanging bolts. Make sure that the hanging bolts
are M10 in size.
• Use hole-in anchors if the hanging bolts already exist;
otherwise use embedded inserts and embedded founda-
tion bolts so that they will withstand the weight of the unit.
Adjust the distance to the ceiling surface in advance.
Installation example
Indoor unit
Note) All the above parts are field supplied.
6
Ceiling slab
Anchor
Long nut or turn-buckle
Hanging bolt
5.

INDOOR UNIT INSTALLATION

〈It may be easier to install accessories (sold separately)
before installing the indoor unit. Refer to the installation
manuals provided to the accessories as well.〉
Be sure to use the accessories and specified parts for
installation work.
(1) Temporally install the indoor unit.
• Connect the hanging brackets to the hanging bolts. Be
sure to use and tighten the nut and washer (11) for each
hanging bracket from both upper and lower sides of the
hanging bracket. (Refer to Fig. 3) At that time, the fall of
the washer (11) for the hanging bracket can be pre-
vented if the washing fixing plate (9) is used.
[Fixing hanging brackets]
Part to be procured in the field
Tighten from above and below
(Double nut)
[Fixing method of washers]
Insert
Washer fixing plate (9)
(accessory)
CAUTION
• During the installation work, perform the curing of the air
outlet and protect the resin drain pan of the indoor unit
from the intrusion of foreign substances, such as weld-
ing spatters.
Otherwise, water leakage may occur as a result of damage,
such as hole damage, to the resin drain pan.
(2) Make adjustments so that the unit will be in the right posi-
tion.
(3) Check the level of the unit.
(4) Remove the washer fixing plates for the falling prevention of
the washers for the hanging brackets, tighten the nuts on
the upper side, and securely fix the unit.
Level
Washer (11) (accessory)
Nut on the upper side
Fig. 3
Hanging bracket
Bottom of product
Vinyl tube
English

Advertisement

Table of Contents
loading

Table of Contents