(D) When outdoor units are stacked
(1)
When an obstruction is present on the air outlet
side
NOTE
1.
Only two outdoor units can be stacked.
2.
About 4 in. is required as the drain piping size for the upper
outdoor unit.
3.
Close the area Z (gap between the upper outdoor unit and
the lower outdoor unit) so that the outlet air does not by-
pass there.
(2)
When an obstruction is present on the air inlet side
NOTE
1.
Only two outdoor units can be stacked.
2.
About 4 in. is required as the drain piping size for the upper
outdoor unit.
3.
Close the area Z (gap between the upper outdoor unit and
the lower outdoor unit) so that the outlet air does not by-
pass there.
(E) When outdoor units are installed in rows (on the roof-
top, etc.)
(1)
When one outdoor unit is installed in each row
English
Z
Z
(2)
When two or more outdoor units are installed side
by side
The dimensional relationship between H, L and A is as
shown in the table below.
0 < L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
H < L
5.
CAUTIONS ON INSTALLATION
•
Before installation, confi rm the strength and levelness of the
foundation so that vibrations and noise are not generated.
•
Fix the outdoor unit securely on a rigid base with foundation
bolts as shown in the foundation drawing below.
(Prepare 4 sets of commercially available M12-type or
equivalent foundation bolts, nuts and washers.)
•
Use resin washers to prevent the paint from being scratched
off and rusting.
•
The foundation bolts should be protruded by 15/16 in.
(Refer to fi gure)
Resin
washer
〈〈Drain treatment〉〉
•
In a location where drain from the outdoor unit may cause
troubles (for example, where drainage may splash on gen-
eral passersby), perform the drain piping work using the
drain plug (optional).
•
For drain treatment, space of at least 4 in. is required under
the bottom frame of the outdoor unit.
•
In the drain piping work, make sure that drainage is dis-
charged securely.
(When routing the piping downward, check for water leak-
age.)
Air outlet side
5 1/2
Bottom view
(unit: inch)
1 7/8
16 5/8
24 1/8
L
A
10
12
Installation is not allowed.
15/16
5 1/2
24 3/8
Drain hole
8