Cautions On Installation - Daikin FHQ18PVJU Installation Manual

Split system ceiling suspended type
Hide thumbs Also See for FHQ18PVJU:
Table of Contents

Advertisement

Available languages

Available languages

The dimensional relationship between H, L and A is as
shown in the table below.
0 < L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
H < L
Install the frame to achieve "L ≤ H".
NOTE
1.
Close the area under the frame so that the outlet air does
not bypass there.
2.
Only two outdoor units can be installed side by side.
(D) When outdoor units are stacked
(1)
When an obstruction is present on the air outlet
side
NOTE
1.
Only two outdoor units can be stacked.
2.
About 4 in. is required as the drain piping size for the upper
outdoor unit.
3.
Close the area Z (gap between the upper outdoor unit and
the lower outdoor unit) so that the outlet air does not by-
pass there.
(2)
When an obstruction is present on the air inlet side
NOTE
1.
Only two outdoor units can be stacked.
2.
About 4 in. is required as the drain piping size for the upper
outdoor unit.
3.
Close the area Z (gap between the upper outdoor unit and
the lower outdoor unit) so that the outlet air does not by-
pass there.
English
L
A
10
12
Z
Z
(E) When outdoor units are installed in rows (on the roof-
top, etc.)
(1)
When one outdoor unit is installed in each row
(2)
When two or more outdoor units are installed side
by side
The dimensional relationship between H, L and A is as
shown in the table below.
0 < L ≤ 1/2H
L ≤ H
1/2H < L ≤ H
H < L
5.

CAUTIONS ON INSTALLATION

Before installation, confi rm the strength and levelness of the
foundation so that vibrations and noise are not generated.
Fix the outdoor unit securely on a rigid base with foundation
bolts as shown in the foundation drawing below.
(Prepare 4 sets of commercially available M12-type or
equivalent foundation bolts, nuts and washers.)
Use resin washers to prevent the paint from being scratched
off and rusting.
The foundation bolts should be protruded by 15/16 in.
(Refer to fi gure)
Resin
washer
〈〈Drain treatment〉〉
In a location where drain from the outdoor unit may cause
troubles (for example, where drainage may splash on gen-
eral passersby), perform the drain piping work using the
drain plug (optional).
L
A
10
12
Installation is not allowed.
15/16
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fhq24pvjuFhq30pvju

Table of Contents