Advertisement

4.
Access panels should be removed only by Toshiba Field Service personnel.
5.
Turn the power on only after installing ALL of the covers.
6.
If the UPS should emit smoke, produce an unusual odor, or make sound, turn the power off immediately.
When operating in the inverter mode, placing the breaker in the OFF position will switch the UPS to the
battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be
in the bypass mode at the time that the breaker is placed in the OFF position for the UPS to shutdown
power to the load.
Wait at least 5 minutes after an Emergency Power Off (EPO) before resetting the UPS breaker. This
NOTICE
allows the UPS circuitry to fully discharge. The UPS could be damaged if the unit is not fully discharged
before the breaker is reset.
Hardwire Connections
Remove the terminal cover plate on the lower-left back side of the UPS. Follow the directions below in wiring the unit.
Jumper Position for 208V input
1
2
3
L1
L2
G
208 Vin
Jumper Position for 240V input
1
2
3
L1
L2
G
240 Vin
NOTE 1 – If AC input power is 208 Vac rated, short terminals 11 and 12 with the provided jumper wire/bus bar. DO NOT jumper terminal 13 to
12 or 11. Factory Setting is 208Vac. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.
NOTE 2 – If AC input power is 240 Vac rated, short terminals 12 and 13 with the provided jumper wire/bus bar. DO NOT jumper terminal 11 to
12 or 13. Use the jumper wire/bus strip provided by Toshiba. DO NOT add any additional jumpers.
NOTE 3 – 8-22 kVA UPSs have a jumper bus bar.
DO NOT jumper Terminals 11 and 13 together. Doing so could damage the UPS.
NOTICE
Output Terminal Connections for 208/240Vin
Connect the load to the output terminals according the load voltage requirements.
See the Output Terminal Voltages table to the right.
1600EP Series Quick Installation Guide
4
5
6
7
X1
X2
N
X3
120 V
120 V
208 V
240 V
4
5
6
7
X1
X2
N
X3
120 V
120 V
208 V
240 V
12
13
14
8
11
COM 240
EPO1
G
208
Jumper
8
11
12
13
14
COM 240
G
208
EPO1
Jumper
Vout
120 Vout
208 Vout
240 Vout
15
16
17
EPO2
REMOTE1
REMOTE2
15
16
17
EPO2
REMOTE1
REMOTE2
Output Terminal Voltages
Terminal Lugs
X3 - N, or X1 - N
X3 - X2
X3 - X1
3
3