High Density Cabling; Figure 4 Cable Design For The Msfp Patch Cables For The Fc8-64 High Density - Brocade Communications Systems DCX 8510-4 Hardware Reference Manual

Hide thumbs Also See for DCX 8510-4:
Table of Contents

Advertisement

2
Cable management
NOTE
You should not use tie wraps with optical cables because they are easily overtightened and can
damage the optic fibers.
ATTENTION
Do not route the cables in front of the air exhaust vent, which is located at the top of the port side
of the chassis.If you are using the Port Side Exhaust Kit with your Brocade DCX 8510-4, there is also
an exhaust vent at the bottom of the port side of the chassis. Use the cable management finger
assemblies to keep the cables away from this exhaust vent as well.

High density cabling

The FC8-64 high density port blade cannot use the standard LC cables because the pitch between
optics in the new mini-SFP (mSFP) transceiver is smaller than in standard SFPs. Patch cables and
panels can be used to attach standard size cabling to the blade if necessary.
the mSFP to SFP patch cable. Refer to "Best Practices Guide: High Density Cable Management
Solutions" (available at http://www.brocade.com) for cable management guidelines for
high-density port solutions, cable and patch panel part numbers.
1
2
FIGURE 4
Note that the duplex clip on the mSFP end of the cable is black for easier recognition. See the
appendix for a listing of the qualified mSFP optical cables for the FC8-64 port blade.
20
Plan for rack space required for cable management before installing the switch.
Leave at least 1 m (3.28 ft) of slack for each port cable. This provides room to remove and
replace the switch, allows for inadvertent movement of the rack, and helps prevent the
cables from being bent to less than the minimum bend radius.
If you are using Brocade ISL Trunking, consider grouping cables by trunking groups. The
cables used in trunking groups must meet specific requirements, as described in the
Fabric OS Administrator's Guide.
For easier maintenance, label the fiber-optic cables and record the devices to which they
are connected.
Keep LEDs visible by routing port cables and other cables away from the LEDs.
®
Use Velcro
type straps to secure and organize fiber-optic cables.
mSFP connector
Duplex clip (black)
Cable design for the mSFP patch cables for the FC8-64 high density port blade
3
1.6 mm cable
4
SFP connector
Brocade DCX 8510-4 Backbone Hardware Reference Manual
Figure 4
illustrates
53-1002177-06

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents