Figure B-5. Split-Phase 120/240 Volts Ac Circuit Connection - NEC Express5800/320Ma Planning Manual

Hide thumbs Also See for Express5800/320Ma:
Table of Contents

Advertisement

Circuit Wiring Diagrams
Figure B-5
shows a split-phase 120/240-volts AC circuit connection. Note that this
application requires a double-pole circuit breaker.

Figure B-5. Split-Phase 120/240 Volts AC Circuit Connection

Circuit A or B
Single system: 20A maximum
PDU: 30A maximum
B-6
Express5800/320Ma: Site Planning Guide
Power Cord
X
Y
G (PE)
To power input A or B
L1
240V
L2
120V
120V
N
0V
G (PE)