Space Planning; Room Requirements - NEC Express5800/320Ma Planning Manual

Hide thumbs Also See for Express5800/320Ma:
Table of Contents

Advertisement

For information about planning sufficient space for your Express5800/320Ma 3.2 GHz,
3.6 GHz, or Dual-Core system, see:
"Room Requirements" on page 3-1
"Planning for Cables" on page 3-2

Room Requirements

To ensure that the installation site provides a properly equipped, cooled, and sized
environment, make sure that the site:
Provides clearances for air circulation and servicing the system
Locate the front and rear of the system at least 2.5 ft (0.76m) away from walls and
other obstructions.
Maintains reasonable temperature and humidity levels and has a thermometer and
humidistat to monitor room temperature and humidity
Is as free of dust as possible
Dust buildup in the system can impede air circulation and heat transfer, causing
components to become less reliable as the ambient temperature rises.
Provides a table or desktop for external devices such as a telephone, keyboard,
and mouse
Provides cutouts in the floor for routing cables, if the site has an elevated floor
!
See
Appendix A, "System Specifications"
C A U T I O N
Do not place the system in an area of high electrostatic
discharge. Static electricity may damage components.
Do not locate components near transformers or other
electromagnetic devices.

Space Planning

for the dimensions of system components.
Chapter 3
Space Planning
3-1
3-