11. POINTS TO DIAGNOSE
11-1. Indoor Unit Alarm Signal
Alarm Signal
Misconnection of inter-unit wiring
Room temp. thermistor is defective
Power Lamp Heat exch. thermistor is defective
Flashing
Fan motor is defective
Amp. current is high
Amp. current is low
Heat exch. thermistor detects high temp
11-2. Manifold Pressure
Outdoor Unit
Fuel
CG1411
Natural gas
To set manifold pressure there are 2 settings – low pressure and high pressure.
Use SW1 to move to the 2 modes used to adjust the two pressures.
Press SW1 1 time for low pressure.
Press SW1 2 times for high pressure.
Press SW1 3 times for normal operation.
Use VR1 to set the low, lighting pressure and VR2 to set the high pressure.
Step 1: Set low pressure
1. Press SW1 and hold until LEDs 4 and 5 flash.
2. Adjust the low pressure with VR1 to 0.63 inches of water column.
Step 2: Set high pressure
1. Press SW1 again and LEDs 1 and 2 will flash.
2. Adjust pressure with VR2 to 3.43 inches of water column.
Step 3: Set lighting pressure
Lighting pressure will be set automatically from Step 1 and Step 2.
NOTE
Check these settings 2 or 3 times to insure all are correct then reset until no LEDs flash.
Error Meaning
Inlet Pressure W.C. (kPa)
7.0 (1.74)
Operation
Heating • Cooling • Dry
Connect correctly
Heating • Cooling • Dry
Normal: 9 – 11 kΩ at 50°F
Heating • Cooling • Dry
Normal: 100 – 120 kΩ at 50°F
Heating • Cooling • Dry
Alarm signal appears in 1 min.
Heating • Cooling • Dry
More than 17 amp.
Heating • Cooling • Dry
Less than 0.8 amp.
Heating
More than 154°F (68°C)
Manifold Pressure W.C. (kPa)
Low
LD4, 5 Flashing
LD2, 3 Flashing
0.63 (0.157)
3.43 (0.853)
50
Information
4 – 6 kΩ at 77°F
50 – 60 kΩ at 77°F
High
Lighting (10 sec.)
(verification)
2.32 (0.579)