Haier CA0070AANB Installation & Operation Manual page 6

Air cooled module water chiller
Table of Contents

Advertisement

Refrigerant charge
Refrigeration system (circuit quantity)
Refrigeration control method
Water side heat exchager
Air side heat exchanger
Water flow
Water resistance
Water pipe diameter
Noise level
Net weight
Running weight
Casing
Nominal working condition (cooling ):water inlet temp. 12 ℃ , water outlet temp. 7℃, ambient temp. 35℃
Nominal working condition (heating ):water inlet temp. 40 ℃ , water outlet temp. 45 ℃, ambient temp. (DB)7℃, (WB)6℃
The permitted range of voltage is 380±10%
In the unit there are two protector, air breaker for compressor motor is GV2-M22C,whose parameter is overload
current:20~25A,short circuit current:327A,415V; air breaker for fan motor is GV2-M08C, whose parameter is overload
current:2.5~4A,short circuit current:51A,400V.
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter. The noise level is measured at 2meter in front of the unit, 1.5 meter high to the ground.
When starting up the complete unit, the compressor will start up one by one and will not start up together.
height
mm
kg
m3/h
kPa
mm
DB/(A) 63
kg
kg
1920
10
1
thermostatic expansion valve
shell & tube heat exchanger, working pressure 1.0MPa
cross finned coil, inner grooved copper pipe&dydrophilic
aluminum finned coil
6
80
65
560
660
polyester painted galvanized steel plate, ivory white
HAIER CHILLER
1920
10*2
2
12
80
65
65
800
925

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ca0035aanbCa0035manbCa0070manb

Table of Contents