Haier CA0070AANB Installation & Operation Manual page 21

Air cooled module water chiller
Hide thumbs

Advertisement

2.3 B3 permitted minimum temperature of out water in cooling 4℃
2.4 B4 permitted max. temperature of out water in heating
2.5 B5 ambient temperature limit in cooling
2.6 B6 ambient temperature limit in heating
2.7 B7 ambient temperature permitting starting electric heating
2.8 B8 temperature difference between electric heating start
and stop
3)
Type C - protection
3.1 C1 high pressure malfunction protection temperature
3.2 C2 high pressure malfunction resume temperature
3.3 C3 malfunction auto resume time
3.4 C4 water pump malfunction detection time delay
3.5 C5 low voltage malfunction detection time delay
3.6 C6 fan motor overload malfunction detection time delay
3.7 C7 compressor overload detection time delay
4)
Type D - working parameter
4.1 D1 temperature adjustment period
4.2 D2 time interval of external equipment action
4.3 D3 protection signal shield byte
4.4 D4 temperature undetected byte 0 air discharge 1 out water 00
4.5 D5 when cooling, the unit not checking the ambient
temperature
5)
Type E - password setting
5.1 E1 factory password
5.2 E2 decode 1
5.3 E3 decode 2
5.4 E4 trial run period 1
5.5 E5 trail run period 2
5.6 E6 accumulated working time
5.7 E7 product serial number setting
6)
F type-Module Number Setting
HAIER CHILLER
0~5℃
80℃
50~90℃
10℃
1~10℃
25℃
10~30℃
12℃
5~20℃
8℃
3~15℃
125℃
85~135℃
60℃
50~80℃
4s
2~20s
4s
2~20s
5s
2~20s
5s
0~20s
5s
0~20s
1min
1~4min
3s
2~20s
00
00
0: checking
1: no checking
Product serial No.
12 34
12 34
9999×10h
EE
invalid
9999×10h
EE
invalid
00 00×10h
00 00
0000~9999
(ABCDEFGH)
A
EE
shows
EE
shows