Baxi MULTIFIT Evacuated Tube Collector Kit Instructions page 33

Evacuated tube collector 10 tube additional pitched roof kit
Hide thumbs Also See for MULTIFIT Evacuated Tube Collector:
Table of Contents

Advertisement

Indication
© Baxi Heating UK Ltd 2011
Press
or
to scroll
up or down to the required sub function.
The icon will flash, press
select the function. Reset by pressing
or
for
increase/decrease values. Press
and
appears,
ok?
press
to confirm and
disappears.
Description
Switching on / off switch output A1 (solar circulation pump)
Switching on / off switch output A2 (pump2)
Switching on / off switch output A3 (heating)
14.0
Commissioning of solar controller
to
14.6
Menu "Manual operation"
For commissioning, service and test purposes the solar primary
system can be manually operated. For this purpose the switch
outputs may be disconnected or connected.
WARNING - During manual operation there is no automatic
ok?
regulation of the system. Temperature control is isolated.
System temperature could be extremely high.During manual
operation there is no automatic regulation of the system.
To avoid inadmissible operating states this mode of operation
changes into "Indication" after approximately 8 hours and the
automatic regulation is activated again.
Value range
0 = off
1 = on
0 = off
1 = on
0 = off
1 = on
33