Selecting the system scheme
System schemes, see from page 51.

Setting system parameters

Press the following keys:
1.
"ANL" and the display will
show the respective scheme.
2.
until the required parameter is
shown (see table on
page 49).

Resetting system parameters

If a different system scheme is selected,
all parameters are returned to their orig-
inal state.

Carrying out a relay test

Press the following keys:
1.
"ANL" and the display will
show the respective scheme.
2.
Select "HND 1" or "HND 2".
HND 1 Relay 1
HND 2 Relay 2
3. OK
"SET" flashes.
(cont.)
3. OK
"SET" flashes.
4.
/
for the selected value.
5. OK
to confirm.
4.
/
for the required setting.
Auto Control mode
On
in (100%)
"Æ" and "Â" or "Ã" are
displayed and "¨"
flashes.
OFF OFF
"Æ" is shown and "¨"
flashes.
5. OK
to confirm.
6. After the relay test has been comple-
ted, select "Auto".
Commissioning
45