The Settings In Detail; Operator Section; Operation And Display; Heating Circuits - Siemens Albatros2 RVS46 Series User Manual

Zone controler
Hide thumbs Also See for Albatros2 RVS46 Series:
Table of Contents

Advertisement

Operation and display

Data:read
Data:write

mixing valve control

Mixing valve Xp
Mixing valve Tn
Siemens Schweiz AG
HVAC Products
2

The settings in detail

2.1 Operator section

Line no.
Operating line
30
Data:read
No
Yes
31
Data:write
No
Yes
The setting data of all operating levels are copied from the controller to the memory of
the operator unit. This means that previous data in the operator unit will be overwritten.
With the exception of the data listed below, the setting data of all operating levels are
transferred from the memory of the operator unit to the connected controller. Previous
setting data in the controller will be overwritten.
The following data will not be overwritten:
Line no.
Operating line
3
Year
130
Room unit 1
131
Room unit 2
132
Outside sensor
133
Repeater
134
Operator unit
135
Service unit
138
Delete all devices
516
default values
536
default values
556
default values
576
default values
6222
Device hours run
6600
device address
6601
Segment address
6650
Outside temp source

2.2 Heating circuits

Line no.
HC1
HC2
HC3P
835
1135
836
1136
The proportional band defines within which change of the control variable ∆x (∆T of the
flow) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
∆y at a given change of the controlled variable ∆x.
The integral action time is the period of time the controller's I-part would require to
produce the same change of the manipulated variable as the P-part
User Manual OEM
The settings in detail
Operating line
Mixing valve Xp
Mixing valve Tn
15/26
CE1U2353en01a
22. November 2006

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents