Pump H1/h2; Pump H1; Primary Controller / System Pump; Flow Temperature Setpoint Limitations - Siemens Albatros2 RVS46 Series User Manual

Zone controler.
Hide thumbs

Advertisement

pump H1

H1/H2 DHW charging
priority

flow temperature setpoint limitations

Siemens Schweiz AG
HVAC Products
Example:
0
5
6
Time program 4 / DHW
For DHW heating, time switch program 4 of the local controller is used. The set
switching times of that program are used to switch between the nominal DHW setpoint
and the reduced DHW setpoint. This way, the DHW is heated independently of the
heating circuits.
Example:
0
6

2.4 Pump H1/H2

Line no.
Operating line
H1
H2
2008 2033 H1/H2 DHW charging priority
Off
¦ On
When using this setting, the connected pump H1/H2 can be excluded from / included in
the effect of DHW charging priority.
In the case of a ventilation system, for example, it is thus possible to ensure a constant
supply of heat with no impact from DHW charging priority.

2.5 Primary controller / system pump

Line no.
Operating line
2110
Flow temp setpoint min
2111
Flow temp setpoint max
Using this limitation, a temperature range for the flow temperature setpoint can be
defined. If the requested flow temperature setpoint reaches the relevant limit and the
heat request increases or decreases, the flow temperature setpoint will be maintained
at the maximum or minimum limit.
User Manual OEM
The settings in detail
12
16 17
24
12
18
h
h
24
CE1U2353en01a
22. November 2006
17/26