Section 6

DIAGNOSING WATER LEVEL CONTROL CIRCUITRY

Problem: Water Trough Overfilling During The
Freeze Cycle
Step 1 Start a new freeze sequence by moving the ICE/
OFF/CLEAN toggle switch to OFF, then back to ICE. (if
water flows with the switch off, check the water inlet
valve).
This restart must be done prior to performing
diagnostic procedures. This assures the ice
machine is not in a freeze cycle water inlet valve
safety shut off mode. You must complete the entire
diagnostic procedure within 6 minutes of starting.
Is water flowing into
the water trough?
NO
YES
YES
Part Number 80-1630-3
Important
GREEN WATER LEVEL LIGHT
WATER LEVEL PROBE CONNECTION
Step 3 Jumper wire connected from control board terminal to ground
The Water Level
Light is:
ON
ON
OFF
Step 2 Wait until the freeze cycle starts
(the freeze cycle starts when the water pump energizes).
Step 3 Disconnect water level probe wire from control
board and connect a jumper from the control board
terminal and any cabinet ground, then refer to chart.
For the test to work properly you must wait until the
freeze cycle starts, prior to connecting the jumper
wire. If you restart the test you must disconnect the
jumper wire, restart the ice machine, (step 1) and
then reinstall the jumper wire after the compressor
starts.
Step 3
The Water Inlet Valve
Solenoid Coil is:
De-Energized
Energized
De-Energized
Electrical System
Important
Cause
The water level probe is causing the problem.
Clean or replace the water level probe.
The control board is causing the problem.
The water fill valve is causing the problem.
SV3135
6-23