Heat & Glo 550TRSI-AUF Owner's Manual page 76

Hide thumbs Also See for 550TRSI-AUF:
Table of Contents

Advertisement

B. Vent Components Diagrams (continued)
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). The heat shield is designed to be
used on a wall 4 in. to 7-1/4 in. (102 mm to 184 mm) thick. If wall thickness is less than 4 in. (102 mm)
the existing heat shields must be field trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a
DVP-HSM-B will be required.
15-1/8 in.
(384 mm)
12 in.
(305 mm)
SLP-SNKD
Snorkel
Termination Cap
SL-2DVP
Adapter
DVP-HE
Heat Exchanger
Figure 16.7 SLP Series Vent Components
76
8 in.
(203 mm)
SLP-TRAP
Horizontal Termination Cap
SLP-CCS-BK
Cathedral Ceiling
Support Box-Black
Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF • 2079-980 Rev. R • 2/13
Heat
Shield
Term Cap
Max
Effective
Trap1
Length
Trap2
SLP-TVHW
Vertical
Termination Cap
DVP-2SL
Adapter
SLP-DCF-BK
Ceiling Firestop
Black
Minimum
Maximum
Effective Length
Effective Length
3-1/8 in.
4-3/4 in.
79 mm
121 mm
5-1/4 in.
9-1/4 in.
133 mm
235 mm
DVP-FBHT
Horizontal
Termination Cap
26 in.
660 mm
DVP-HSM-B
Extended Heat Shield
SLP-WT-BK
Wall Thimble-Black

Advertisement

Table of Contents
loading

This manual is also suitable for:

550trsilp-auf

Table of Contents