Install The Ceiling Firestop - Heat & Glo 550TRSI-AUF Owner's Manual

Hide thumbs Also See for 550TRSI-AUF:
Table of Contents

Advertisement

C. Install the Ceiling Firestop
A ceiling firestop MUST be used between
floors and attics.
• DVP pipe only - Frame an opening 10 in.
x 10 in. (254 mm by 254 mm) whenever the
vent penetrates a ceiling/floor (see Figure
8.3).
• SLP pipe only - Frame opening 9 in. x 9
in. (229 mm x 229 mm) whenever the vent
penetrates a ceiling/floor (see Figure 8.3).
• Frame the area with the same sized lumber
as used in ceiling/floor joist.
• The ceiling firestop may be installed above or
below the ceiling joists when installed with a
attic insulation shield. It must be under joists
between floors that are not insulated. Refer
to Figure 8.4.
• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-
lation around the vent. Insulation must be kept
back from the pipe to prevent overheating.
Figure 8.3 Installing Ceiling Firestop
INSTALLED BELOW CEILING
Figure 8.4 Installing the Attic Shield
Heat & Glo • 550TRSI-AUF, 550TRSILP-AUF • 2079-980 Rev. R • 2/13
INSTALL ATTIC INSULATION SHIELDS
BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
3 FASTENERS
PER SIDE
CEILING FIRESTOP
ATTIC ABOVE
A
A
PIPE
A
DVP
10 in. (254 mm)
SLP
9 in. (229 mm)
CEILING FIRESTOP
INSTALLED ABOVE CEILING
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

550trsilp-auf

Table of Contents