Chimney Requirements - Heatilator EC36 Installation & Operating Instructions Manual

Woodburning fireplace
Table of Contents

Advertisement

3. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 12 in. from the fireplace opening. See Figure 6. If
you are using a decorative surround constructed of combustible material, it must be located within the shaded area
defined in Figure 6. Short stub walls are also acceptable if they are contained within the shaded area.
When planning your fireplace location, the chimney construction and necessary clearances must be considered. The
fireplace system and chimney components have been tested to provide flexibility in construction. The following figures
are the minimum distances from the base of the fireplace.
12
Cat. #
A
E/EC36 36 in. [914mm] 41 in. [1041mm]
E/EC39 39 in. [991mm]
44 in. [1118mm]
E/EC42 42 in. [1067mm] 47 in. [1194mm]
E. CHIMNEY REQUIREMENTS
1.
Minimum overall straight height
2.
Minimum height with offset/return
3.
Maximum height
4.
Maximum chimney length between an offset and return
5.
Maximum distance between chimney stabilizers
6.
Double offset/return minimum height
7.
Maximum unsupported chimney length between the offset and return
8.
Maximum straight unsupported chimney height above the fireplace
EC SERIES INSTALLATION INSTRUCTIONS
B
Figure 6 - Sidewalls and Surrounds
17339 Rev L
13 ft
14.5 ft
90 ft
20 ft
35 ft
24 ft
6 ft
35 ft
08/04