Unusually Tight Construction; Appliances Located In Confined Spaces; Air Openings Diagrams - PEERLESS SERIES DE Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

4
Unusually
Tight Construction:
For equipment
located in buildings of unusually tight
construction
as defined on the previous page,
provide air for combustion
and ventilation
using the
methods described in 5a or 5b below.
5. Appliances
Located
in Confined
Spaces:
a. All air from inside the building: Provide two
permanent
openings communicating
directly with
an additional
room or rooms of sufficient volume
so that the combined
volume of all spaces meets
the criteria for an unconfined
space. Use the total
input of all gas utilization equipment
installed in
the combined
space in making this
determination.
Size each opening with a minimum
free area of
one square inch per I000 Btu/hr. of the total
rating of all gas utilization equipment
in the
confined space, but not less than I00 square
inches. Begin with one opening
12 inches from
the top, and begin the other opening within 12
inches of the bottom of the enclosure. See Figure
I. Provide air openings with minimum
dimensions
not less than three (3) inches.
b. All air from oulside the building. Connect the
confined space with the outdoors
in accordance
with methods i) or it) below. Provide air openings
with minimum dimensions
not less than three (3)
inches. Where ducts are used, make certain that
they are the same cross-sectional
area as the free
area of the openings to which they connect.
Provide two permanent
openings,
one
commencing
within 12 inches of the top and
one commencing
within 12 inches of the
bottom of the enclosure. Connect the
openings directly or by ducts, with the
outdoors or spaces (crawl or attic) that freely
communicate
with the outdoors.
Where directly communicating
with the
outdoors
(see Figure 2) or where
communicating
to the outdoors
through
vertical ducts (see Figure 3), size each
opening with a minimum
free area of one (I)
square inch per 4000 Btu!hr, of total rating of
all equipment
in the enclosure.
Where communicating
with the outdoors
through horizontal
ducts, size each opening
with a minimum
free area of one (i) square
inch per 2000 Blu/hn of total input rating of
all equipment
in the enclosure. See Figure 4.
TWO AIR OPENINGS: _-
Minimum
\
Free Area Each =
\
1 in2per 1000 Btuh
\
at Least 100 in2
t
12" max
3" rain
\
BUILDING
Mast communicate freely
with outdoors
Must not be under
negativepressure
_-
3" rain
12" max
Figure
1:
Air Openings
- All Air from
Indoors
TWO AIR OPENINGS:
Minimum
Free Area Each =
1 in2per 4000 Btuh
Figure
2:
Air Openings
- All Air Directly
from
Outdoors
12" max
Minimum
in _ per 4000 Btuh
Figure
3:
Air Openings
- All Air from Outdoors
through
Vertical
Ducts

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

De-03De-04De-05De-06

Table of Contents