Boiler Troubleshooting Guide (Burners Functioning) - PEERLESS SERIES DE Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

Table
8:
Boiler
Troubleshooting
Guide
(Burners
Functioning)
Burners
not functioning
Burners
will not shut
down
Flashback
or burning
at orifice spuds
Delayed ignition.
Condensation
at boiler
vent connector/fan•
See Figure 26
i Defi,cflve gas valve
2. Short circuit.
1. Manifold gas pressure too low.
2 [mproperly
sized/drilled
orifice spuds.
3 Leaking gas valve.
4. Burrs on orifice
5. Low supply gas pressure,
1 Insufficient pilot flame.
2. Pilot burner/orifice
clogged.
3. Overfiring,
4. Misaligned burners or pilot
1. Vent pipe not sloped towards vent terminal•
See
Figure
26
i Use Figure 26 to troubleshoot
intermittent
ignition gas valve
Replace if necessary.
2 Check and correct wiring
] Adjust to proper pressure
2 Install correct spuds.
3. Replace valve.
4. Remove burrs.
5. Contact gas supplier if natural gas Adjust
regulator if LP gas.
1 Increase pilot gas flow.
2, Clean pilot burner and orifice
3. Reduce rate to input on rating label•
i
4. Realign burners or pilot
i
i
I. Install condensate
_'ap per vent manufacturer's
instructions.
2. Slope vent pipe towards vent terminal.
Boiler not heating
i
properly,
i
i
Fumes or gas odors
1. Underfiring.
2 Limit set too low.
3. Air in system.
4. Circulator
malfunctioning.
5. Circulation system clogged
6 Incorrect thermostat
heat anticipator
setting.
1, Increase rate to input on rating label.
2. Reset limit to higher setting.
3. Vent air from all points in system,
4. Check circulator, replace if necessary.
5. Shut down and cool boiler, drain and flush
system•
6. Adjust heat anticipator.
I Leaks in gas piping or fittings,
2. Leaks in gas service line or meter
3. Obstructed
chimney.
4. Obstructed
flueways or vent.
5. Draft problem
in boiler room.
6. Overfiring.
I Locate and repair or replace
2. Shut down boiler and notiO gas provider.
3. Check, repair and!or clean chimney.
4. Clean flueways or vent and remove obstructions.
5. Check air supply, ventilation and venting system•
7. Reduce rate to input on rating label•
28