Installation
Instructions
DUCTWORK
LENGTH AND DUCT FITTINGS
NOTE: Do not exceed
150 foot maximum
permissible
equivalent
lengths!
Flexible
ducting:
If flexible
metal
ducting
is used, all equivalent
feet values
in the table
should
be
doubled.
The flexible
metal
duct should
be straight
and smooth
and extended
as much as possible.
(_DO
NOT use flexible
plastic
ducting.
Add equivalent
lengths
for all duct
pieces and transitions
used to ensure
that the duct run does not
exceed the maximum
150 feet.
im
n
m
1 ft. (per
foot length)
1 ft. (per
foot length)
15ft.
I_]f_i
_
II_
_
i0_l
L=_111_'1_
6" Round
3W" x 10"
3V4" x 10"
24 ft.
Wall Cap
21 ft,
Straight
90 ° Flat Elbow
with
Damper
(_
6" Round
[_
3V4" x 10"
6"
to 3V4" x 10"
7 ft.
Wall Cap
27 ft.
90 ° Elbow
Transition
with
Damper
3V4" x 10"
_
6"
to 6" Round
5 ft.
]_
6" Round
20 ft.
45 ° Elbow
9 ft.
Transition
Roof Cap
6" Round
to 3V4" x 10"
20 ft,
3W" x 10"
Transition
6" Round
24 ft.
90 ° Elbow
16 ft.
90 ° Elbow
Roof Vent
SHOULD NOT EXCEED 150 EQUIVALENT
FEET
*Equivalent
lengths
of duct pieces are based on actual tests conducted
by GE Evaluation
Engineering
and reflect requirements
for good venting
performance.
See chart for CFM Duct Length,
i
13