Map Descriptor Example 4 - Analog Output 1 (Area Machine) - FieldServer Lutron Machine FS-8700-97 Driver Manual

Fieldserver technologies computer driver instruction manual
Table of Contents

Advertisement

FS-8700-97 Lutron Machine Manual

5.3.7 Map Descriptor Example 4 - Analog Output 1 (Area Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on the Lutron eLumen panel. Scenes
range from 0 to 65535 and area numbers range from 0 to 511
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
SMD000_AO
, Analog_Output
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name
Sel_scene_0
, Analog_Output
The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified under Data_Array_Name. Area
numbers increase with the Length field in association with increasing offset into the Data Array.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
, Data_Array_Offset
, Function
, Node_Name
, 0
, Passive
, Virtual_BCU_11
, Data_Array_Offset
, Function
, Node_Name
, 0
, Awt
, LUT_GRF6_0
Page 13 of 24
, Data_Type
, Object_ID
, AO
, 1
, Grafik_Command
, Area
, Length
, Sel_Scene_In_Area
, 0
, 512
, Length
, Relinquish_Default
, 512
, 0

Advertisement