General Settings

To access the General Settings menus:
1.
SETUP
SETUP
F4
2.
3.
4.
ENTER
The actual settings are shown in the SETUP entry screen. Use the key operations
described above to change an item.
Read below how to make adjustments:
User name/address: see section USER PREFerences.
1
Date, Time: Use F3 to choose between date and time adjustment. Use
2
the arrow keys to adjust date, date representation MM/DD/YY
(Month/Day/Year) or DD/MM/YY (Day/Month/Year), and time. With
3
a GPS receiver connected and F2 set to GPS ON, date and time are
synchronized automatically. Time zone and daylight saving ON/OFF
can also be set. Press F1 to access the GPS test menu that informs you
about reception quality. Press Function key F5 – OK to confirm and
return to the previous menu.
Config: selection of 10 wiring configurations. Selection is done with
4
F1, F2, F3 and the arrow keys. Then press Function key F5 – OK to
confirm and to enter a screen showing how to connect the Analyzer to
the power system. When ready press Function key F5 to return to the
SETUP entry screen.
Vnom: adjustment of Nominal Voltage. Use the arrow keys to select
5
100 V, 120 V, 230 V, 400 V or any desired value. Press Function key
F5 – OK to confirm.