Inspecting The Rotor Assembly - Briggs & Stratton 1938 Operator's Manual

Table of Contents

Advertisement

Service &
Troubleshooting
Guide
Home Generator
Systems
__'ggs&
Stm_o,'
Model 1938 (I 0kW) Generator
Assembly
_
_
_
Inspecting
The Rotor
Assembly
It is not possible to check the serviceable condition
of a
rotor
assembly without
de-soldering
specific corn ponents.
The reading that is obtained by the process shown in figure
71 only gives the resistance value of the rotor
winding.
It does not show if the diode or the thermal protection
device is serviceable. The only way to determine
if these
corn ponents are serviceable, is to de-solder them from the
electrical
circuit of the rotor assembly and check them
individually.
For this reason, rotor
replacement
should only be
considered
when all other possible faults have been
eliminated.
OTES
53