Troubleshooting
o• If continuity
is measured:
• Select MANUAl.
at the AUTO/OFF/MANUAL
switch
and allow engine to stabilize.
• Measure voltage and frequency at Pin #10, Wire #66
and Ground as shown in figure 33.
High Oil Temperature:
(Seven
Blinks [ ......
o])
The contacts of the temperature
switch are normally open
(NO).
If the engine oil temperature
exceeds approximately
140°C (284°F), the switch contacts close and the engine
shuts down.
Common
causes for this condition
include:
- Running the unit with all access doors removed
- Obstructed
air inlet or exhaust port
- Debris in the engine cylinder cooling fins
When the problem is corrected,
reset the fault detection
system:
• Place the AUTO/OFF/MANUAL
switch in the OFF
position for 30 seconds or more.
High Oil Temperature
Troubleshooting
Procedure:
• Remove Wire #95 from the Oil Temperature
Sensor as
shown in figure 34.
18-22VAC & 60-62 Hz
........................................................................................................................................................
_ should be measured.
NOTE:
Follow the Frequency Measurement
instructions that apply to the type of meter you are
using.
•• If frequency and voltage are correct:
• Verify that CMA is not picking up a signal elsewhere.
Verify
Ground
connection
on CMA
circuit
board.
(See Figure
32)
• Replace CMA Circuit Board.
•• If frequency is not correct:
Check engine RPM.
• Set engine RPM to 3600, as specified in the BRIGGS &
STRATTON
engine service manual.
• Start engine.
• • If engine starts and runs:
• Verify engine is not overheating.
This can be accomplished by checking the following:
• Verify that the cooling intake is clear of obstructions.
• Check that the engine has the proper
amount and type
of oil.
• See that the engine cooling fins are not clogged.
32