Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path
trapInputFrequencyOutOfRangeOk
Input under or over frequency ok
UPS.PowerConverter.Input[1].PresentStatus.FrequencyOutOfRange = 0
trapRemoteEmergencyPowerOff
Remote emergency power off
UPS.PowerSummary.PresentStatus.EmergencyStop = 1
trapReturnFromEmergencyPowerOff
Return from remote emergency power off
UPS.PowerSummary.PresentStatus.EmergencyStop = 0
trapOutputOverload
Output overload
UPS.PowerSummary.PresentStatus.Overload = 1
trapOutputOverloadOk
Output overload ok
UPS.PowerSummary.PresentStatus.Overload = 0
trapLevel2Overload
Level 2 overload
UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 1
trapLevel2OverloadOk
Level 2 overload ok
UPS.PowerConverter.Output.Overload[1].PresentStatus.OverThreshold = 0
trapLevel3Overload
Level 3 overload
UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 1
trapLevel3OverloadOk
Level 3 overload ok
UPS.PowerConverter.Output.Overload[2].PresentStatus.OverThreshold = 0
trapPosDCLinkOverVoltage
Positive DC link over voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 1
trapPosDCLinkOverVoltageOk
Positive DC link over voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.HighPositiveDCBusVoltage = 0
Trap
Trap Level
16
1
17
2
18
1
19
2
20
1
21
2
22
1
23
3
24
1
25
2
26
1
|
71
MIB Objects